Ceiling suspended unit / Unit for open ceiling installation UV42F.N20 / UUD1.U30 1Ф

Category:

Heating capacity: 13.5 kW.

Cooling capacity: 12.1 kW.

Performance at -10°C: 9.5 kW.


  • Single-phase (1F) outdoor unit
  • Single-phase (1F) indoor unit

IMPORTANT! A wireless remote control is included in the kit.

COMBINATION
Capacity Cooling Min. / Rated / Max. kW 4.8 / 12.1 / 14.2
Heating 5.4 / 13.5 / 15.8
Power Input (Set) Cooling Min. / Rated / Max. kW 0.80 / 3.90 / 5.07
Heating 0.80 / 3.75 / 4.88
Running Current Cooling Rated A 17.0
Heating 16.5
HONOR / COP kWh / kWh 3.10 / 3.60
SEER / SCOP kWh / kWh 6.3 / 4.1
Pdesign Cooling @ 35°C kW 12.1
Heating @ -10°C 9.5
Seasonal Energy Label Cooling / Heating – / –
Annual Energy Consumption Cooling / Heating kWh 1,152 / 3,244
Dehumidification Rate l/h 5.5
ODU Sound Pressure Level Cooling / Heating Rated dB(A) 51 / 52
ODU Sound Power Level Cooling Rated dB(A) 69
Piping Connections Liquid mm (inch) ø 9.52(3/8)
Gas mm (inch) ø 15.88 (5/8)
Connections Method Flared
Operation Range (Outdoor) Cooling My. / Max. °C – 20 / 52
Heating – 25 / 18
INDOOR UV42F.N20
Power Supply ø / V / Hz 1 / 220-240 / 50
Power Input (IDU) H / M / L IN 50 / 35 / 28
Air Flow Rate H / M / L m3/min 28 / 24 / 20
Dimensions Body W x H x D mm 1,600 / 235 / 690
Weight Body kg 36.7
Sound Pressure Level Cooling H / M / L dB(A) 46 / 43 / 40
Sound Power Level Cooling Max. dB(A) 62
Piping Connections Drain (Natural Drainage) O.D / I.D mm ø 25.0 / 20.5
Drain (Using Drain Pump) ø 32.0 / 26.0
OUTDOOR UUD1.U30
Power Supply ø / V / Hz 1 / 220-240 / 50
Circuit Breaker Min. A 40
Power Supply Cable (Included Eart) No x mm3 3C x 6.0
Dimensios Net W x H x D mm 950 / 1,380 / 330
Weight Net kg 85
Compressor Type Inverter Scroll
Refrigerant Type R32
Fan Air Flow Rate Rated m3/min x No 55 x 2
Total Piping Lenght My. / Max. m 5 / 85
Piping Elevation IDU – ODU Max. m 30