Nominal Capacity and Nominal Input | HU051MR.U44 | ||||
Condition | Outdoor Temp (°С) DB / WB | Leaving Water Temp. (°С) | – | ||
Capacity | Cooling | 35 / 24 | 18 | kW | 5,5 |
35 / 24 | 7 | kW | 5,5 | ||
Heating | 7.6 | 35 | kW | 5,5 | |
HONOR | Cooling | 35 / 24 | 18 | In/In | 4,6 |
35 / 24 | 7 | In/In | 2,8 | ||
COP | Heating | 7.6 | 35 | In/In | 4,9 |
7.6 | 55 | In/In | 3,5 | ||
2.1 | 35 | In/In | 3,52 | ||
SCOP (Low temp. Average) | 4,65 | ||||
SCOP (High temp. Average) | 3,23 | ||||
Rated Water Flow Rate (at LWT 35°С) | LPM | 15,8 |
Electrical Specifications | HU051MR.U44 | ||
Power Supply | V, Ø, Hz | 220-240, 1, 50 | |
Maximum Running Current | Cooling | A | 14,2 |
Heating | A | 14,2 | |
Peak Control Running Current | Cooling | A | 13 |
Heating | A | 13 | |
Rated Running Current | Cooling | A | 5,3 |
Heating | A | 5 | |
Circuit breaker | A | 16 | |
Wiring Connections | Power Supply Cable (included Earth) | No × mm2 | 3 × 4.0 (H07RN-F) |
Technical Specifications | HU051MR.U44 | |||
Sound Power Level | Heating | Rated | dB(A) | 60 |
Low noise | dB(A) | 58 | ||
Sound Pressure Level (at 1m) | Heating | Rated | dB(A) | 50 |
Dimensions | Unit | W × H × D | mm | 950 × 834 × 330 |
Packed Unit | W × H × D | mm | 1,065 × 618 × 461 | |
Weight | Unit | kg | 60 | |
Packed Unit | kg | 65 |
Outdoor Units | HU051MR.U44 | |||
Operation Range (Outdoor Temperature) | Cooling | My. ~ Max. | °C DB | 5 ~ 48 |
Heating | My. ~ Max. | °C DB | -25 ~ 35 | |
Compressor | Type | – | Hermetic Sealed Scroll | |
Model | Model × No. | RJB036MAA × 1 | ||
Motor Type | – | BLDC | ||
Displacement | cm 3 /Rev. | 31,6 | ||
Refrigerant | Type | – | R32 | |
GWP (Global Warming Potential) | – | 675 | ||
Precharged Amount | g | 1 500 | ||
t-CO2 eq. | – | 1,013 | ||
Control | – | Electronic Expansion Valve | ||
Refrigerant Oil | Type | – | FW68D | |
Charged Volume | cc × No. | 1 100 | ||
Piping Connections | Gas | Type | Flare | |
mm(Inch) | F 15.88 (5/8) | |||
Liquid | Type | Flare | ||
mm(Inch) | F 9.52 (3/8) | |||
Piping Length | Standard | m | 5 | |
Max. | m | 50 | ||
Piping Level Difference | Max. | m | 30 | |
Chargeless-Pipe Length | m | 10 | ||
Additional Charging Volume | g/m | 30 | ||
Heat Exchanger | Quantity | YES | 1 | |
Specification | Row | YES | 2 | |
Column | YES | 38 | ||
FPI | YES | 14 | ||
Fan | Type | – | Propeller | |
Air Flow Rate | Rated | m3 /min × No. | 60.0 × 1 | |
Fan Motor | Type | – | BLDC | |
Output | W × No. | 124 × 1 |
Indoor Unit | Â HN091MR.NK5 | |||
Operation Range (Leaving Water Temperature) | Cooling | My. ~ Max. | °C DB | 5 ~ 27 |
Heating | My. ~ Max. | °C DB | 15 ~ 65 | |
DHW * | My. ~ Max. | °C DB | 15 ~ 80 | |
Water Pump | Type | – | Canned type for hot water circulation | |
Model | GRUNDFOS UPM3K 20-75 CHBL | |||
Motor Type | – | BLDC | ||
Steps of Pump Performance | – | Variable capacity 10% to 100% | ||
Power input | My. ~ Max. | IN | 3 ~ 60 | |
Heat Exchanger | Type | – | Brazed Plate HEX | |
Quantity | 1 | |||
Number of Plate | YES | 54 | ||
Water Volume | ˜ | 0,7 | ||
Flow Sensor | Type | – | Vortex | |
Model | – | SIKA VVX20 | ||
Measuring Range | My. ~ Max. | ˜/min | 5 ~ 80 | |
Flow (Trigger point) | Min. | ˜/min | 7 | |
Expansion Vessel | Volume | Max. | ˜ | 8 |
Water pressure | Max. | bar | 3 | |
Water pressure | Pre-charged | bar | 1 | |
Strainer | Mesh size | – | 28 mesh | |
Material | – | Stainless Steel | ||
Relief valve | Pressure Limit | Upper Limit | bar | 3 |
Piping Connections | Water Circuit | Inlet | mm(Inch) | Male PT 25(1″) |
Outlet | mm(Inch) | Male PT 25(1″) | ||
Refrigerant Circuit | Gas | mm(Inch) | F 15.88 (5/8) | |
Liquid | mm(Inch) | F 9.52 (3/8) | ||
Wiring Connections | Communication Cable (included Earth) | No × mm2 | 4 × 0.75 (H07RN-F) | |
Sound Power Level | Heating | Rated | dB(A) | 44 |
Dimensions | Unit | W × H × D | mm | 490 × 850 × 315 |
Packed Unit | W × H × D | mm | 563 ×1082 × 375 | |
Weight | Unit | kg | 41 | |
Packed Unit | kg | 47 |