Outdoor unit | FM40AH UO2 | |||
Capacity | Cooling | Min.~Nom.~Max. | kW | 2.8 ~ 11.2 ~ 13.5 |
Min.~Nom.~Max. | Btu/h | 9,600 ~ 38,200 ~ 46,000 | ||
Heating | Min.~Nom.~Max. | kW | 3.1 ~ 12.5 ~ 15.0 | |
Min.~Nom.~Max. | Btu/h | 10,560 ~ 42,700 ~ 51,200 | ||
Supply power | Cooling | Min.~Nom.~Max. | kW | 0.78 ~ 2.73 ~ 4.15 |
Heating | Min.~Nom.~Max. | kW | 0.82 ~ 2.81 ~ 4.45 | |
SEER / SCOP | Wh/Wh | 6.10 / 3.90 | ||
Seasonal energy class | Cooling / Heating | – | A++ / A | |
Annual consumption | Cooling / Heating | kWh | 643 / 4,236 | |
Power supply | V , Ø , Hz | 220-240, 1, 50 | ||
Operating current | Cooling | Min.~Nom.~Max. | A | 3.5 ~ 12.1 ~ 18.4 |
Heating | Min.~Nom.~Max. | A | 3.6 ~ 12.5 ~ 19.7 | |
Starting current | Cooling | Max. | A | – |
Heating | Max. | A | – | |
Cable connections | Power cord (with grounding) | No. x mm2 (AWG) | 3C x 3.5 (10) | |
Power and communication cable (with grounding) | External ~ distribution box | No. x mm2 (AWG) | 4C x 1.25 (16) | |
Combination | Total capacity of indoor units | kBtu/h | 52 | |
Number of indoor units | YES | 7 | ||
Number of distribution boxes | YES | 2 | ||
Box color | – | Warm Gray | ||
Dimensions | W x H x D | mm | 950 × 1,170 × 330 | |
W x H x D | inch | 37-13/32 x 46-1/16 x 13 | ||
Weight (net) | kg (lbs) | 82 (180.8) | ||
Compressor | Type | – | Twin Rotary | |
Model | Model x No. | GPT442MBA x 1 | ||
Engine type | – | BLDC | ||
Power | W x No. | 4,000 (at 60Hz) x 1 | ||
Refrigerant | Type | – | R410A | |
Loaded quantity | g (oz) | 3,800 (134.0) | ||
Pipe length without refilling | Main pipe | m (ft) | 5 (16.4) | |
Pipes after box | 35 (114.8) | |||
Recharge | Main pipe | m (oz/ft) | 20 (0.22) | |
Pipes after box | 50 (0.54) | |||
Control | – | Electronic Expansion Valve | ||
Refrigerant oil | Type | – | FVC68D | |
Loaded quantity | cc x No. | 1,300 x 1 | ||
Heat exchanger | #1_(Row x Column x Lamella per inch) x No. | – | (2 x 32 x 14) x 1 | |
#2_(Row x Column x Lamella per inch) x No. | (2 x 22 x 14) x 1 | |||
Fan | Type | – | Propeller | |
Air flow rate | m3 /min x No. | 45 x 2 | ||
Fan motor | Type | BLDC | ||
Power | W x No. | 85.4 x 2 | ||
Sound pressure level | Cooling | Nominally | dB(A) | 53 |
Heating | Nominally | dB(A) | 55 | |
Sound power level | Cooling | Max. | dB(A) | 67 |
Pipe connections | Liquid | Outer diam. | mm(inch) x No. | Ø 9.52 (3/8) |
Gas | Outer diam. | mm(inch) x No. | Ø 19.05 (3/4) | |
Pipeline length | Total pipe path | Max. | m (ft) | 100 (328.1) |
Pipeline before the boxes | Max. | m (ft) | 50 (164.0) | |
Pipe path from box to body | Max. | m (ft) | 50 (164.0) | |
Maximum length from box to body | Max. | m (ft) | 15 (49.2) | |
Maximum elevation gain | External ~ Internal | Max. | m (ft) | 30 (98.4) |
Internal ~ External | Max. | m (ft) | 15 (49.2) | |
Operating mode (outdoor temperature) | Cooling | Min~Max. | ℃ DB (℉ DB) | -10 (14.0) ~ 48 (118.4) |
Heating | Min~Max. | ℃ WB (℉ WB) | -18 (-0.4) ~ 18 (64.4) |
Outdoor unit with the ability to connect up to 7 units FM40AH.U34
3 years warranty
Refrigerant R410A
Cooling capacity: 12.3
Heating power: 13.5
Possibility of connecting R410 and R32 refrigerant units
IMPORTANT: TO CONNECT MORE THAN 1 UNIT, YOU NEED TO PURCHASE A JUNCTION BOX, “U”-SHAPED SPLITTER OR KIT.
- Perfect solution for multiple rooms
- Energy efficient
- Improved heat exchanger
- Exceptional durability
- Comfort and convenience
- Rapid cooling
- Fast heating
- Silent mode for night time
- Easy and quick viewing via display board
Possibility of diagnostics via phone with additional accessory